0

Control Systems Mcqs

Q:

How many types of controllers and compensators are there respectively?

A) 4, 3 B) 3, 4
C) 4, 5 D) 5, 4
 
Answer & Explanation Answer: A) 4, 3

Explanation: There are 4 types of controllers namely PID, PI, PD. There are 3 types of compensators namely Lag, Lead & Lag-Lead compensators.

View Answer Discuss

55
Q:

What is the need for a controller?

A) Receive control signals B) Transmit control signals
C) Modify control signals D) Create control signals
 
Answer & Explanation Answer: C) Modify control signals

Explanation: Controller is needed to modify control signals for better control action. Some control signals are raw signals which can’t function properly so we use controllers for modifying them.

View Answer Discuss

51
Q:

Actuator is the basic component of an automatic control system.

A) False B) True
 
Answer & Explanation Answer: B) True

Explanation: There are 5 basic components of an automatic control system. They are error detector, amplifier, actuator, plant, and sensor. So, Actuator is a basic component of automatic control system.

View Answer Discuss

50
Q:

For a unity feedback control system, the open loop transfer function G(s) = 10(s+2)/s²(s+1). What is the acceleration error constant?

A) Infinity B) 5
C) 10 D) 20
 
Answer & Explanation Answer: D) 20

Explanation: As limit s tends to zero s² G(s) H(s) = s2 G(s) = 10*2/1 = 20. Therefore we get the value of Ka as 20 and both kv and ks are infinity.

View Answer Discuss

75
Q:

A performance index must offer selectivity.

A) True B) False
 
Answer & Explanation Answer: A) True

Explanation: It must offer selectivity, that is, an optimal adjustment of parameters must clearly distinguish non optimal adjustment of parameters. If there was no selectivity we would not have been able to distinguish between parameters.

View Answer Discuss

58
Q:

The open loop transfer function for a unit feedback system is G(s) = K/s(sT+1). By what factor the amplitude gain K should be reduced so that the peak overshoot becomes 25% from 75%?

A) 75 B) 25
C) 20 D) 10
 
Answer & Explanation Answer: C) 20

Explanation: The peak overshoot is decreased by increasing the damping ratio. The damping ratio is increased by reducing the gain K by same proportion and for decreasing the peak overshoot from 75% to 25% the factor of amplitude becomes 19.6% which is approximately 20%.

View Answer Discuss

106
Q:

What is the analogous electrical element of Frictional coefficient (B) in Force-Current Analogy for mechanical translational system?

A) Resistance B) Conductance
C) Flux D) Voltage
 
Answer & Explanation Answer: B) Conductance

Explanation: As Resistance is the analogous element of B in F-V analogy so here it is the reciprocal of resistance, conductance is the answer. Force voltage analogy means both the equations will have differential equation of the same form.

View Answer Discuss

40
Q:

A unity feedback system has an open loop transfer function G(s) =25/s(s+8). What is the percentage of it’s peak overshoot?

A) 0.13% B) 1.13%
C) 1.26% D) 1.52%
 
Answer & Explanation Answer: D) 1.52%

Explanation: Damping ratio is calculated from the characteristic equation and placing that value in the formula for peak overshoot Mp = e3.14DR (1- DR2) we get the answer. Peak overshoot arises especially in the step response of the systems such as low pass filters which are band limited.

View Answer Discuss

63